APC GALAXY VX Uninterruptible Power Supply UPS - 480V External battery system, 400 V 3 phase, Schneider Electric, 0...3333 ft
Express Shipping
out of 5 stars
Key Features
Wide Operating Altitude Range – Engineered to deliver reliable backup power performance at altitudes up to 3333 ft, ensuring stability in diverse installation environments.
-
400 V 3-Phase Output – Provides balanced, efficient, and stable power distribution for mission-critical applications in data centers, offices, and industrial facilities.
-
External Battery System – Compatible with Li-Ion and VRLA technologies, enabling scalable runtime options and optimized energy management.
-
Advanced Power Protection – Offers surge protection, voltage conditioning, and emergency backup to secure sensitive IT and network equipment against disruptions.
-
Safe & Smart Operation – Built with Schneider Electric’s robust safety standards, ensuring electrical safety, emergency response readiness, and intelligent power management.
Package Dimensions
Specifications
Q&A
Warranty
wholesale buying guide
General
- Maximum Configurable Power in VA
- 750 kVA
- Battery Type
- External battery system
- Battery Voltage
- 480V
- End of Discharge Battery Voltage
- 384 V DC
- Product or Component Type
- Uninterruptible power supply (UPS)
- Battery power in VAH
- 0 VAh runtime
- Main Input Voltage
- 400 V 3 phase
- Main Output Voltage
- 400 V 3 phase
- Color
- White
Tech Specs
- Standards
- IBC 2012 IEC 62040-1-1 IEC 62040-2 IEC 62040-3 IEC 62040-4 ISTA 2B
- Crest factor
- 3 with THC <5%
- Maximum Short Circuit Withstand (Icw)
- 100 kA
- Weight
- 2030 kg
- Dimensions
- L (35.4 in) x W (94.5 in) x H (77.6 in)
- Provided Equipment
- Installation guide Start-Up Service
- Other Output Voltages
- 380 V 415 V 440 V
- Other Input Voltage
- 380 V 415 V 440 V
- Lead time
- Special Order - Call for Quoted Lead Times
- Operating altitude
- 0...3333 ft
- Storage altitude
- 0…50000 ft (0…15240 m)
- Input Total Harmonic Distortion
- Less than 3% for full load
- IP degree of protection
- IP20
- Ambient Air Temperature for Storage
- 5…104 °F (-15…40 °C)
- Overload Operation
- 10 minutes @ 125% and 60 seconds @ 150%
- Input Frequency
- 40 - 70 Hz
- Relative Humidity
- 0…95 % non-condensing
- Ambient Air Temperature for Operation
- 32…104 °F (0…40 °C)
- Waveform Type
- Sine wave
- Output Frequency
- 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal not synced 60 Hz +/- 0.1 % for 60 Hz nominal not synced
- Load power factor
- From 0.7 leading to 0.7 lagging without any derating
- Presentation
- Highly efficient, scalable, 3-phase power protection with flexible operating modes and ECOnversion™ for large facilities, data centers, and business critical applications.
- Control panel
- 7" touch screen display
- Heat dissipation
- 80387 Btu/h
- Acoustic level
- 69.5 dBA
| Products |
|---|
| Choose your plan |
- 250 nits
- 16:9
- 60 Hz
- 400 nits
- 60 Hz
- Tilt, Height, Pivot
- Tilt
- 250 nits
- 1ms MPRT
- 250 nits
- Tilt
- 5 ms (GtG)
- External battery system
- 480V
- 384 V DC
- 480-576VDC
- 150 kVA
- 384 V DC
- 480...576 V DC
- 50 kVA
- 384 V DC
- 750 kVA
- External battery system
- 480V

VIEWSONIC VG2748A Monitor - 27" FHD (1920 x 1080), IPS, Height, Tilt, Swivel, Pivot, HDMI, DP, VGA, 250nits, 60Hz

LG ULTRAFINE 27UP850K-W Monitor - 27” UHD (3840 x 2160), IPS, Tilt, Height, Pivot, HDMI, DP, USB-C, 400nits, 60Hz

VIEWSONIC VA2432-MHD Monitor - 24" FHD (1920 x 1080), IPS, Tilt, HDMI, DP, VGA, 250nits, 100Hz

LG 24U421A-B Curved Monitor - 24" FHD (1920 x 1080), VA, Tilt, HDMI, USB-C, 250nits, 100Hz

APC GALAXY VX Uninterruptible Power Supply UPS - 480V External battery system, 400 V 3 phase, Schneider Electric, 137523 Btu/h, 1000 kVA

APC GALAXY VS Uninterruptible Power Supply UPS - 480-576VDC External battery system Li-Ion (Lithium Ion) VRLA, 400 V 3 phase, Schneider Electric, 150 kVA

APC GALAXY VS Uninterruptible Power Supply UPS - 480...576 V DC External battery system Li-Ion (Lithium-Ion)VRLA, 400 V 3 phases, Schneider Electric