APC GALAXY VS Uninterruptible Power Supply UPS - 480V Internal modular battery VRLA, 400 V 3 phase, Schneider Electric
Express Shipping
out of 5 stars
Key Features
High-Performance UPS – Provides reliable uninterruptible power for critical applications, ensuring continuous operation in offices, data centers, and industrial setups.
-
Internal Modular VRLA Battery – Features a modular design for easy maintenance, scalable runtime, and improved overall efficiency during power outages.
-
Stable 400V 3-Phase Output – Delivers consistent three-phase power, protecting sensitive equipment and supporting high-demand electrical loads.
-
Advanced Power Protection – Offers surge protection, power conditioning, and electrical safety features to prevent damage to connected devices.
-
Schneider Electric Engineering & Management – Built under Schneider Electric standards, enabling smart power management, network monitoring, and emergency backup for mission-critical systems.
Package Dimensions
Specifications
Q&A
Warranty
wholesale buying guide
General
- Battery Voltage
- 480V
- Output Voltage THD
- < 1% linear load and < 3% non-linear load
- End of Discharge Battery Voltage
- 384 V DC
- Product or Component Type
- Uninterruptible power supply (UPS)
- Battery power in VAH
- 0 VAh runtime
- Maximum Configurable Power in VA
- 40 kVA
- Main Input Voltage
- 400 V 3 phase
- Main Output Voltage
- 400 V 3 phase
- Output voltage tolerance
- +/- 5% after 2ms +/-1% after 50ms
- Color
- White
Tech Specs
- Maximum Input Current per Phase
- 72 A
- Efficiency at full load
- 340...460 V 400 V
- Weight
- 296 kg
- Dimensions
- L (33.3 in) x W (21.7 in) x H (77.6 in)
- Presentation
- Highly efficient, easy-to-deploy 40kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 5 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5x8 start-up service and one additional power module for N+1 redundancy.
- Maximum Short Circuit Withstand (Icw)
- 65 kA
- Input Frequency
- 40 - 70 Hz
- Provided Equipment
- Dust filter Installation manual Integrated network management Start-Up Service EcoStruxure Ready
- Lead time
- Usually Ships within 2 Weeks
- Input Total Harmonic Distortion
- Less than 6 % for full load
- Load power factor
- From 0.7 leading to 0.7 lagging without any derating
- Input Power Factor at Full Load
- 0.99
- Max Configurable Power (Watts)
- 40 kW
- Harmonic distortion
- Less than 3%
- Output Frequency
- 50 Hz sync to mains 60 Hz sync to mains
- Crest factor
- 2.5
- Waveform Type
- Sine wave
- Output voltage tolerance
- +/- 5% after 2ms +/-1% after 50ms
- Output Voltage THD
- < 1% linear load and < 3% non-linear load
- Overload Operation
- 10 minutes @ 125% and 60 seconds @ 150%
- Bypass type
- Built-in Static Bypass
- Standards
- IEC 62040-1-1 IEC 62040-2 OSHPD
- Ambient Air Temperature for Operation
- 32…104 °F (0…40 °C)
- Relative Humidity
- 0…95 % non-condensing
- Operating altitude
- 0...3300 ft
- Ambient Air Temperature for Storage
- 5…104 °F (-15…40 °C)
- Storage Relative Humidity
- 10…80 % non-condensing
- Storage altitude
- 0…10000 ft (0…3048 m)
- Acoustic level
- 54 dBA
- Heat dissipation
- 4412 Btu/h
- IP degree of protection
- IP20
- Control panel
- Touch Screen LCD User Interface
Products |
---|
Choose your plan |
- 80 kVA
- Internal modular battery VRLA
- 480V
- 750 kVA
- External battery system
- 480V
- 480V
- < 1% linear load and < 3% non-linear load
- 384 V DC
- Internal modular battery VRLA
- 50 kVA
- 208 V 3 phase
- 1250 kVA
- External battery system
- 480V
- External battery system
- 480V
- 384 V DC



APC GALAXY VS Uninterruptible Power Supply UPS - 480V Internal modular battery VRLA, 480 V 3 phase, Schneider Electric, 80 kW

APC GALAXY VX Uninterruptible Power Supply UPS - 480V External battery system, 400 V 3 phase, Schneider Electric, 175802 Btuh, 750 Kva

APC GALAXY VS Uninterruptible Power Supply UPS - 480V Internal modular battery VRLA, 400 V 3 phase, Schneider Electric

APC GALAXY VS Uninterruptible Power Supply UPS - 384-480VDC External battery system Li-Ion (Lithium Ion) VRLA, 208 V 3 phase, Schneider Electric, 5kVA

APC GALAXY VX Uninterruptible Power Supply UPS - 480V External battery system, 400 V 3 phase, Schneider Electric, 174332 Btu/h