APC GALAXY VS Uninterruptible Power Supply UPS - 384-576VDC External battery system Li-Ion (Lithium Ion) VRLA, 400 V 3 phase, Schneider Electric, 0...3300 ft
Express Shipping
out of 5 stars
Key Features
High-Capacity Power Protection – Delivers reliable 400 V 3-phase output with 384–576 VDC external Li-Ion and VRLA battery support for extended backup.
-
Flexible External Battery System – Scalable Li-Ion and VRLA options provide long runtime, reduced footprint, and optimized lifecycle management.
-
Advanced Safety & Reliability – Ensures surge protection, power conditioning, and electrical safety for mission-critical applications.
-
Smart Energy Management – Integrated monitoring and power management features enable real-time control and network management.
-
Designed for Altitude Resilience – Fully operational up to 3300 ft, ensuring stable performance across diverse installation environments.
Package Dimensions
Specifications
Q&A
Warranty
wholesale buying guide
General
- Maximum Configurable Power in VA
- 80 kVA
- Output Voltage THD
- < 1% linear load and < 3% non-linear load
- Product or Component Type
- Uninterruptible power supply (UPS)
- End of Discharge Battery Voltage
- 307 V DC
- Battery Type
- External battery system Li-Ion (Lithium Ion) VRLA
- Output voltage tolerance
- +/-1% after 50ms
- Battery Voltage
- 384-576VDC
- Main Input Voltage
- 400 V 3 phase
- Main Output Voltage
- 400 V 3 phase
- Color
- White
Tech Specs
- Operating altitude
- 0...3300 ft
- Ambient Air Temperature for Storage
- -13…131 °F (-25…55 °C)
- Storage Relative Humidity
- 10…80 % non-condensing
- Acoustic level
- 68 dBA
- Heat dissipation
- 8394 Btu/h
- IP degree of protection
- IP21
- Control panel
- Touch Screen LCD User Interface
- Presentation
- Highly efficient, easy-to-deploy 80kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and halogen-free cables. Marine certified.
- Lead time
- Usually Ships within 2 Weeks
- Main Input Voltage
- 380 V 415 V
- Provided Equipment
- Dust filter EcoStruxure IT ready (UPS) Installation guide Integrated network management Power modules ship installed Start-Up Service
- Dimensions
- L (33.3 in) x W (20.5 in) x H (58.5 in)
- Weight
- 250 kg
- Input Frequency
- 40 - 70 Hz
- Efficiency at full load
- 340...460 V 400 V
- Input Total Harmonic Distortion
- Less than 3% for full load
- Load power factor
- From 0.7 leading to 0.7 lagging without any derating
- Crest factor
- 2.5
- Waveform Type
- Sine wave
- Output voltage tolerance
- +/-1% after 50ms
- Overload Operation
- 10 minutes @ 125% and 60 seconds @ 150%
- Standards
- EN/IEC 62040-1 EN/IEC 62040-2 FCC Part 15 class A IEC 60721-4-2 Level 2M2 UL 1778 5th edition
- Ambient Air Temperature for Operation
- 32…104 °F (0…40 °C)
- Relative Humidity
- 0…95 % non-condensing
| Products |
|---|
| Choose your plan |
- 384-480VDC
- < 1% linear load and < 3% non-linear load
- Uninterruptible power supply (UPS)
- Non-Touch
- Black
- IPS
- Non-Touch
- Black
- 24" FHD (1920 x 1080)
- < 1% linear load and < 5% non-linear load
- 40 kVA
- 400 V 3 phase
- Black
- 3h
- 0° to 40°C
- 480-576VDC
- 480 V 3 phase
- 480 V 3 phase
- External battery system
- 480V
- 384 V DC

APC GALAXY VS Uninterruptible Power Supply UPS - 384-480VDC External battery system Li-Ion (Lithium Ion) VRLA, 208 V 3 phase, Schneider Electric

DAHUA LM24-B201S Monitor - 23.8" FHD (1920×1080), IPS, HDMI, VGA, 250 nits, 100Hz


GIGABYTE G24F Gaming Monitor - 24" FHD (1920 x 1080), IPS, HDMI, DP, 300 nits, 180 Hz

APC GALAXY VS Uninterruptible Power Supply UPS - 384-576VDC External battery system Li-Ion (Lithium Ion) VRLA, 400 V 3 phase, Schneider Electric

APC Smart SRT2200XLI UPS - 2200VA, 72V Lead-Acid Battery, 230V Output Voltage, 3 Hours Recharge Time

APC GALAXY VS Uninterruptible Power Supply UPS - 480-576VDC External battery system Li-Ion (Lithium Ion) VRLA, 480 V 3 phase, Schneider Electric, 150 kVA