Key Features
Powerful 100 kVA Capacity with 400 V 3-Phase Output – Provides robust and stable power delivery for data centers, enterprise facilities, and mission-critical environments.
-
External Li-Ion & VRLA Battery System – Supports 480–576 VDC external batteries, offering extended runtime, energy efficiency, and scalable backup options.
-
Complete Power Protection – Ensures surge suppression, voltage stabilization, and backup power, protecting sensitive IT and industrial equipment from outages and power disturbances.
-
Smart Power & Network Management – Features intelligent monitoring, remote diagnostics, and advanced control tools, improving energy management and operational reliability.
-
Enterprise-Grade Reliability – Engineered by Schneider Electric for electrical safety, emergency power, and long-term stability, making it ideal for offices, networks, and industrial applications.
Package Dimensions
Specifications
Q&A
Warranty
wholesale buying guide
General
- Maximum Configurable Power in VA
- 100 kVA
- End of Discharge Battery Voltage
- 384 V DC
- Product or Component Type
- Uninterruptible power supply (UPS)
- Output Voltage THD
- < 1% linear load and < 5% non-linear load
- Main Input Voltage
- 400 V 3 phase
- Main Output Voltage
- 400 V 3 phase
- Battery Voltage
- 480-576VDC
- Battery Type
- External battery system Li-Ion (Lithium Ion) VRLA
- Color
- White
Tech Specs
- IP degree of protection
- IP21
- Control panel
- Touch Screen LCD User Interface
- Presentation
- Highly efficient, easy-to-deploy 100kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and one additional power module for N+1 redundancy.
- Provided Equipment
- Dust filter EcoStruxure IT ready (UPS) Installation guide Integrated network management Power modules ship installed Start-Up Service
- Dimensions
- L (33.3 in) x W (20.5 in) x H (58.5 in)
- Weight
- 290 kg
- Input Frequency
- 40 - 70 Hz
- Efficiency at full load
- 340...460 V 400 V
- Input Total Harmonic Distortion
- Less than 3% for full load
- Load power factor
- From 0.7 leading to 0.7 lagging without any derating
- Output Frequency
- 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal not synced 60 Hz +/- 0.1 % for 60 Hz nominal not synced
- Crest factor
- 2.5
- Waveform Type
- Sine wave
- Output voltage tolerance
- +/-1% after 50ms
- Output Voltage THD
- < 1% linear load and < 5% non-linear load
- Overload Operation
- 10 minutes @ 125% and 60 seconds @ 150%
- Standards
- EN/IEC 62040-1 EN/IEC 62040-2 FCC Part 15 class A IEC 60721-4-2 Level 2M2 UL 1778 5th edition
- Ambient Air Temperature for Operation
- 32…104 °F (0…40 °C)
- Relative Humidity
- 0…95 % non-condensing
- Operating altitude
- 0...3300 ft
- Ambient Air Temperature for Storage
- -13…131 °F (-25…55 °C)
- Storage Relative Humidity
- 10…80 % non-condensing
- Acoustic level
- 68 dBA
- Heat dissipation
- 11373 Btu/h
Products |
---|
Choose your plan |
- Non-Touch
- Black
- 24" FHD (1920 x 1080)
- 32GB
- Android 11
- Bluetooth, Wi-Fi
- Tilt
- 250 nits
- 16:9
- 50 kVA
- 480V
- 480 V 3 phase
- 208 V 3 phase
- 208 V 3 phase
- 384-480VDC
- 60kW 400V
- 60 kVA
- 384 V DC
- 384-480VDC
- < 1% linear load and < 3% non-linear load
- Uninterruptible power supply (UPS)
- Internal modular battery VRLA
- 480V
- 480 V 3 phase

MSI PRO MP251 Monitor - 24" FHD (1920 x 1080), IPS, Height, Swivel, HDMI, VGA, 300 nits, 100 Hz

SAMSUNG WA75C Interactive Display - 75" Landscape 4K (3840 x 2160) 390 nits @ 60Hz LED, Wi-Fi / Bluetooth, Infrared Multi-Touch

VIEWSONIC VA3209-MH Monitor - 32” FHD (1920 x 1080), IPS, Tilt, HDMI, VGA, 250nits, 75Hz

APC GALAXY VS Uninterruptible Power Supply UPS - 480-576VDC External battery system Li-Ion (Lithium Ion) VRLA, 480 V 3 phase, Schneider Electric

APC GALAXY VS Uninterruptible Power Supply UPS - 384-480VDC External battery system Li-Ion (Lithium Ion)VRLA, 208 V 3 phase, Schneider Electric, 75 kVA

APC GALAXY VS Uninterruptible Power Supply UPS - 60kW 400V External battery system Li-Ion (Lithium Ion) VRLA, 400 V 3 phase, Schneider Electric, 108 A

APC GALAXY VS Uninterruptible Power Supply UPS - 384-480VDC External battery system Li-Ion (Lithium Ion) VRLA, 208 V 3 phase, Schneider Electric